Double Interlock Preaction Systems

Double interlock preaction systems are designed for applications such as refrigerated areas that require the maximum degree of protection against an inadvertent operation that could result in unnecessary flooding of the sprinkler system piping.

The double interlock system consists of a deluge valve and swing check valve with releasing trim featuring both a solenoid valve and a dry pilot actuator in a series configuration. The swing check valve isolates the body of the deluge valve from the system air or nitrogen pressure that holds the dry pilot actuator closed. The solenoid valve remains closed until it is electrically energized by a deluge releasing panel that responds to the operation of a fire detection device.

In order to actuate the double interlock preaction system, two independent events, caused by a fire condition, must occur. The sprinkler system piping must lose air or nitrogen pressure due to the operation of one or more sprinklers, and the deluge releasing panel must energize and open the solenoid valve upon the operation of a fire detection device.

The double interlock system will operate only when both the dry pilot actuator and the solenoid valve are open at the same time. Opening of the dry pilot actuator only (for example: a forklift truck accidentally dislodges a sprinkler) or of the solenoid valve only (for example: accidental operation of an electirc manual pull station) will cause an alarm, and will not trip the system or flood the sprinkler system piping.

For more information about fire systems and solutions please use our Fire Systems Enquiries form to have a Wormald representative contact you.

Pneumatic/Electric Shown

Contact Us
 Fire System Enquiries
 General Enquiries